Power Supply Systems

ZTM Series Modular UPS

The ZTT ZTM Series is a fully digital 3-phase modular online double-conversion UPS. Modules and cabinets are combined to cover 10 kVA to 2000 kVA. All variants share: online double conversion, output PF 1, high reliability with component-level protection, intelligent self-diagnosis with large history-record storage, 7" or 10" touch LCD with IoT functions, and USB / RS232 / RS485 / dry-contact interfaces (SNMP, AS400, parallel kit, SPD, LBS optional). The 380/400/415 V family scales to 2.0 MVA — the reference solution for mega data centres. Dedicated 480 V (60 Hz) and 208 V (60 Hz) variants are provided for North-American and low-voltage distribution.

ZTM Series Modular UPS — ZTT power supply system

Features & Characteristics

  • Fully digital control, flexible and robust — modular power modules.
  • 7 & 10 inch touch LCD with IoT functions.
  • High reliability with component-level protection; intelligent system self-diagnosis and rich fault recording.
  • Output power factor 1; efficiency ≥ 96 % in normal mode and battery mode.
  • Certifications — safety IEC 62040-1 / IEC 60950-1; EMS IEC 62040-2 and IEC 61000-4-2/3/4/5.
  • Options — SNMP card, AS400 card, parallel kit, SPD, LBS.
  • Optional 30 A charger module for long-backup applications (on 10–300 kVA modular variants).

Applications

  • Government, finance, IT, education, transportation, broadcasting, medical and energy.
  • Mega data centres — parallel systems up to 1.8 MVA (400 V) or 2.0 MVA (400 V high-power variant).
  • Mission-critical loads requiring THDu < 1 % (linear load) and < 5 % (non-linear).

Technical specifications

Topology
3P/3P online double conversion
Rated input voltage
380 / 400 / 415 Vac (L-L); 220 / 230 / 240 Vac (L-N) — 480 V and 208 V variants available
Input frequency
50 / 60 Hz (40 – 70 Hz range)
Input PF / THDi
> 0.99 / < 3 % @ 100 % linear load
Output PF
1
Output voltage accuracy
± 1.0 %
Output THDu
< 1 % (linear) / < 5 % (non-linear, per IEC 62040-3)
Efficiency
Normal mode ≥ 96 %; Battery mode ≥ 96 %
Overload — inverter
110 % 1 h; 125 % 10 min; 150 % 1 min; > 150 % 200 ms
Operating environment
0 – 40 °C; storage -25 to 70 °C; 0 – 95 % RH non-condensing
System IP degree
IP20
Safety
IEC 62040-1, IEC 60950-1
EMC
IEC 62040-2; IEC 61000-4-2/3/4/5
Communication
USB, RS232, RS485, Dry contact (SNMP / AS400 / parallel / SPD / LBS optional)

ZTM Series — variants and system capacity

VariantPower rangeGrid voltageCabinet module W×D×HReference
ZTM 50~600 kVA50 – 600 kVA per cabinet; up to 1.8 MVA system380/400/415 V, 50/60 Hz600×1000×1600 / 600×1000×2000 / 1200×1100×2000 mmAC200/50 – AC600/60
ZTM 62.5~2000 kVA62.5 – 2000 kVA — up to 2.0 MVA system380/400/415 V, 50/60 HzAC400 – AC2000
ZTM 25~300 kVA25 – 300 kVA380/400/415 V, 50/60 HzAC250/25, AC300/30
ZTM 25~180 kVA25 – 180 kVA380/400/415 V, 50/60 Hz
ZTM 10~120 kVA10 – 120 kVA380/400/415 V, 50/60 Hz
ZTM 60~720 kVA (480 V)60 – 720 kVA — up to 1.8 MVA system480 V, 60 HzAC240/60-H, AC360/60-H, AC600/60-H, AC720/60-H
ZTM 36~360 kVA (208 V)36 – 360 kVA200 / 208 / 220 V, 50/60 HzAC144/36-L, AC216/36-L, AC360/36-L
ZTM 18~108 kVA (208 V)18 – 108 kVA200 / 208 / 220 V, 50/60 HzAC72/18-L, AC108/18-L
ZTM 12~72 kVA (208 V)12 – 72 kVA200 / 208 / 220 V, 50/60 HzAC024/12-L, AC048/12-L, AC72/12-L

Need a specification we don't list?